Hydraulic Generator Controller HGC-2
22
HGC-2 Module Connection notes:-
1. Ensure that the recommended fuses ( FS1 & FS2 ) is installed in the system for full protection and warranty.
2. Use separate cables for each connection as shown above.
3. Connect proportional valve coil cables and run separate from all/any high voltage wires.
4. Ensure that high voltage feedback cable is protected to prevent insulation wear during usage through vibration
Electrical System Connections:
Pin Function
1 +VDC Input Supply
2 0VDC Input Supply
3 +Solenoid Connection O/P
4 -Solenoid Connection O/P
5 AC feedback Neutral I/P
6 AC feedback Line I/P
7 Constant Current Mode enable I/P
8 Controller ENABLE I/P
Beware of HIGH VOLTAGE when operating any
generator system high voltage can be LETHAL
observe ALL laws, by-laws and health & Safety
recommendations for your immediate location,
state and/or country.